| Plan Review Notes For Permit 00030111 |
| Permit Number |
00030111 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** PROVISO **************** | | | | | | 1)NOTE: NEED TO SHOW ALL BRANCH CIRCUT | | | #`S ON PLANS FOR OUTLETS AND LIGHTING. | | | | | | 2)NOTE:PANEL SCHEDULE REFLECT ONLY ONE | | | CIRCUT FOR LIGHTING AND OUTLETS. | | | PLEASE CORRECT FOR THE PROPER AMOUNT OF | | | CIRCUTS REQ`D. | | | | | | 3)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS. PER 110-9/110-10 | | | | | | PROVIDE THE ABOVE INFORMATION BEFORE | | | ROUGH. |
|