| Plan Review Notes For Permit 00030083 |
| Permit Number |
00030083 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: NEED TO SHOW ANY NEW A/C UNITS | | | BEING ADDED FOR ADDITION. | | | | | | 2)NOTE: NEED TO SUBMIT COMPLETE LOAD | | | CALCULATIONS FOR THE EXISTING SERVICE, | | | TO INCLUDE ALL NEW LOADS. | | | | | | 3)NOTE:NEED TO HAVE ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED. PLEASE SHOW. AS REQ`D BY 210-8-A-6 | | | | | | 4)NOTE: NEED TO SHOW NEW CIRCUTS ON | | | PANEL SCHEDULE FOR NEW BATH AS REQ`D BY | | | 210-52D AND 210-11-C-3. | | | | | | 5)NOTE: NEED TO SHOW ANY NEW BLDG. STEEL | | | AS BEING BONDED TO THE GROUNDING ELEC- | | | -TRODE. MUST BE A PART OF GROUNDING | | | SYSTEM. AS PER 250-50 | | | | | | PLEASE SUBMIT FOR REVIEW AND APPROVAL. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXY 8372 |
|