| Plan Review Notes For Permit 00030042 |
| Permit Number |
00030042 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT WATER RISER FOR REVIEW.WATER | | | SUPPLY CONTROL SHALL COMPLY W/SPC SEC. | | | 610.4.1,610.4.2. | | | | | | A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407. | | | | | | DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A)(PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING). | | | | | | A FLOOR DRAIN IS REQD.IN THE TOILET ROOM | | | PER SPC SEC.409.4.1.1(SEE EXCEPTION). | | | | | | BREAK ROOM SINK SHALL COMPLY W/FACBC | | | SEC.4.24.1-4.24.7.CLEAR FLOOR SPACE | | | SHALL BE CENTERED ON THE SINK. | | | | | | WATER CLOSET SHALL BE 18" FROM WALL PER | | | FACBC FIGURE 28. |
|