| Plan Review Notes For Permit 00030042 |
| Permit Number |
00030042 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVIDE CFM INFORMATION FOR DROP IN | | | MRI ROOM AND FOR GE EQUIPMENT ROOM PRIOR | | | TO 1ST INSPECTION | | | FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED FOR EQUIPMENT WITH THE CAPACITY | | | GREATER THAN 2000 CFM WITH NOTIFICATION | | | BY HORN AND STROBE OR TIED TO BLDG FIRE | | | ALARM PER NFPA 90A 4-4.4.2 (OR.3) |
|