Plan Review Notes
Plan Review Notes For Permit 00021424
Permit Number 00021424
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE: NEED TO SHOW A/C EQUIPMENT AND
 ALL DISCONNECTS AND REQ`D RECEPTS.
  
 2)NOTE: MISSING OUTLET PER 210-52E
 INFRONT OF DWELLING.
  
 3)NOTE: MISSINGLIGHTS REQ`D FOR EGRESS
  
  
 4)NOTE: PLEASE LIST ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS BEING GFI/GFI
 PROTECTED.210-8-A-6
  
 5)NOTE: NEED TO SHOW ALL ELECTRICAL AS
 BEING UPDATED. MORE THAN 50% OF ELEC IS
 BEING DONE. PLEASE SHOW ALL ELEC. BEING
 DONE ANDE EXISTING ELECTRICAL.
  
 6)NOTE: MISSING OUTLETS REQ`D BY 210-52
 2`6`12` OF WALL.
  
 7)NOTE: SMOKE DETECTORS ARE REQ`D ALSO
 REQ`D OUTSIDE BEDROOMS.NFPA-72 2-2.1.1.1
 TO INCLUDE SITTING ROOM.
 8)NOTE: MISSING OUTLETS ON SECOND FLOOR
 210-52
  
 9)NOTE: NEED LIGHT FROM MASTER BEDROOM
 AS MEANS OF EGRESS. 210-70
  
 10)NOTE: PLEASE SHOW THE REQ`D BATH(S)
 CIRCUT(S) PER 210-52D/210-11-C-3
 PLEASE LIST ON PANEL SCHEDULE(S)
  
 ALSO PLEASE HAVE PANEL SCHEDULES AND
 SERVICE SHOWN ON SHEETS WITH FRIST AND
 SECOND FLOOR ELECTRIC.
  
 PLEASE HAVE ALL THE ABOVE SUBMITTTED FOR
 REVIEW AND APPROVAL BEFORE ANY ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372