| 2001-01-08 00:00:00 | *************** PROVISO *************** |
| | |
| | 1)NOTE: NEED TO SHOW A/C EQUIPMENT AND |
| | ALL DISCONNECTS AND REQ`D RECEPTS. |
| | |
| | 2)NOTE: MISSING OUTLET PER 210-52E |
| | INFRONT OF DWELLING. |
| | |
| | 3)NOTE: MISSINGLIGHTS REQ`D FOR EGRESS |
| | |
| | |
| | 4)NOTE: PLEASE LIST ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS BEING GFI/GFI |
| | PROTECTED.210-8-A-6 |
| | |
| | 5)NOTE: NEED TO SHOW ALL ELECTRICAL AS |
| | BEING UPDATED. MORE THAN 50% OF ELEC IS |
| | BEING DONE. PLEASE SHOW ALL ELEC. BEING |
| | DONE ANDE EXISTING ELECTRICAL. |
| | |
| | 6)NOTE: MISSING OUTLETS REQ`D BY 210-52 |
| | 2`6`12` OF WALL. |
| | |
| | 7)NOTE: SMOKE DETECTORS ARE REQ`D ALSO |
| | REQ`D OUTSIDE BEDROOMS.NFPA-72 2-2.1.1.1 |
| | TO INCLUDE SITTING ROOM. |
| | 8)NOTE: MISSING OUTLETS ON SECOND FLOOR |
| | 210-52 |
| | |
| | 9)NOTE: NEED LIGHT FROM MASTER BEDROOM |
| | AS MEANS OF EGRESS. 210-70 |
| | |
| | 10)NOTE: PLEASE SHOW THE REQ`D BATH(S) |
| | CIRCUT(S) PER 210-52D/210-11-C-3 |
| | PLEASE LIST ON PANEL SCHEDULE(S) |
| | |
| | ALSO PLEASE HAVE PANEL SCHEDULES AND |
| | SERVICE SHOWN ON SHEETS WITH FRIST AND |
| | SECOND FLOOR ELECTRIC. |
| | |
| | PLEASE HAVE ALL THE ABOVE SUBMITTTED FOR |
| | REVIEW AND APPROVAL BEFORE ANY ROUGH |
| | ELECTRICAL INSPECTION IS CALLED IN. |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL |
| | 659-8096 EXT 8372 |