| 2001-01-08 00:00:00 | DENIED |
| | |
| | 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS FOR EACH |
| | SPECIFIC TYPE OF EXTRIOR WINDOW OR DOOR |
| | TO BE USED. INCLUDING ARCHED WINDOWS |
| | SHOWN ON PLANS. |
| | |
| | 2)PROVIDE EGRESS WINDOW IN BEDROOM. |
| | 97 SBC 1005.4 |
| | |
| | 3)PROVIDE WINDOW SIZES AND TYPES (SINGLE |
| | HUNG,AWNING,ETC.)FOR ALL NEW WINDOWS. |
| | |
| | 4)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS, KEY PLAN AND |
| | INSTALLATION SCHEDULE FOR STORM PANELS. |
| | MISSLE IMPACT PROTECTION IS REQUIRED FOR |
| | ALL EXTERIOR GLAZING. CITY OF WPB |
| | AMENDMENTS TO 97 SBC. |
| | |
| | 5)PROVIDE ATTIC ACCESS PER 97 SBC 2309.6 |
| | |
| | 6)PROVIDE ATTIC VENTIATION.97 SBC 2309.7 |
| | |
| | 7)PROVIDE WALL SECTION AND CONSTRUCTION |
| | DETAILS FOR EXISTING CARPORT THAT IS |
| | BEING ENCLOSED. |
| | |
| | 8)PROVIDE ENERGY CALCULATIONS INCLUDING |
| | MANUAL "J" CALCS. PER 79 FL. ENERGY |
| | EFFICIENCY CODE. |
| | |
| | 9)CONNECTOR LSTA 18 SHOWN ON PLANS |
| | ATTACHING TRUSSES TO WALL IS AN IMPROPER |
| | APPLICATION. USE SIMPSON MTS-12,H6 OR |
| | EQUAL. |
| | |
| | 10)PROVIDE SOIL COMPACTION TEST AT TIME |
| | OF FIRST INSPECTION. |
| | |
| | 11)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY,PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY BLDG. |
| | DEPT. BEFORE A PERMIT TO CONSTRUCT WILL |
| | BE ISSUED. |
| | |
| | 12)PROVIDE POSITIVE AND NEGATIVE WIND- |
| | LOAD PRESSURES FOR EXTERIOR WINDOW AND |
| | DOOR OPENINGS. |
| | |
| | 13)PROVIDE FRAMING DETAILS FOR ARCHED |
| | WINDOWS SHOWN ON PLANS. |
| | |
| | 14)PLEASE RECHECK DISTANCE BETWEEN SHED |
| | AND BED ROOM. FOUNDATION PLAN HAS 4'-0" |
| | AND DIMENSION ON SURVEY IS 2.9' |
| | (18.9'-16.0'=2.9') |