| Plan Review Notes For Permit 00021287 |
| Permit Number |
00021287 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PERMIT APPLICATION SHOWS YOU | | | CHANGING THE SERVICE??? NEED TO SEE | | | ELECTRICAL RISER DIAGRAM, SHOWING SIZE | | | OF EQUIPMENT, WIRES, CONDUITS, AND | | | SUBMIT AIC RATING OF EQUIPMENT MAINS. | | | ALL REQ`D BY 215-5/110-9 | | | | | | 2)NOTE: PLEASE NOTE SMOKE DETECTORS REQ` | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS | | | OF YOUR NEW CONSTRUCTION. | | | | | | 3)NOTE; PLEASE SHOW ON PANEL SCHEDULE | | | THE REQ`D CIRCUTS FOR BATH(S)210-11-C-3 | | | | | | 4)NOTE:IF THERE ARE GOOING TO BE MORE | | | THAN ONE CITCUT IN SHED, THEN YOU NEED | | | DISCONNECT AT THAT STRUCTURE. IF ONLY | | | ONE CIRCUT THEN IT MUST BE GFI. PER | | | 225-30-B-2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|