Plan Review Notes
Plan Review Notes For Permit 00021256
Permit Number 00021256
Review Stop P
Sequence Number 5
Notes
Date Text
2001-01-08 00:00:001)THE TOILET ROOM IN THE TMA SHOW ROOM
 AND THE RECEIVING TOILET ROOM SHALL BE
 HANDICAP ACCESSIBLE PER FACBC SEC.
 4.1.3(11).CLEARLY SHOW COMPLIANCE ON THE
 PLANS.SHOW GRAB BAR HEIGHT,LOCATION,
 HEIGHT OF FIXTURES,CLEARANCES,ETC.
 COMPLY W/FACBC OCT.1997 ED.
  
 2)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC610.4.2.
  
 3)SIZE ALL WASTE,VENT AND WATER LINES ON
 THE DIAGRAM.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 4)INDIRECT WASTES SHALL DISCHARGE INTO
 A FLOOR SINK,NOT FLOOR DRAIN.SPC SEC.
 807.1.
  
 5)A CHECK AND GATE VALVE ARE REQD.ON THE
 SUMPS DISCHARGE PER SPC SEC.717.2.SUMPS
 SHALL BE VENTED PER 717.6.CONNECTION TO
 DRAINAGE SYSTEM SHALL COMPLY W/SPC SEC.
 717.11.
  
 6)FLOOR DRAINS SHALL BE IN FULL VIEW AT
 ALL TIMES PER SPC SEC.409.4.1.2.
  
 7)CONTACT R.COMPO W/CITY OF WPB CENTRAL
 WASTEWATER TREATMENT FACILITY REGARDING
 EFFLUENT FROM FILM PROCESSOR.SUBMIT
 APPROVAL OF SYSTEM W/O NEUTRALIZATION
 TANK FROM R.COMPO.
  
 8)PHOTOLAB RISER-FIXTURES SHALL BE
 VENTED PER SPC 717.4.
  
 9)AN AIR GAP IS REQD.ON THE RTU COND.
 DRAIN PIPING PER SPC SEC.806.
  
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.