| Plan Review Notes For Permit 00021256 |
| Permit Number |
00021256 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | COMPLY W/ALL PREVIOUS COMMENTS DATED | | | 3/5/00 & 5/1/00. | | | | | | SHT.CV-1-"BUILDING CODES"-INSERT CORRECT | | | EDITION OF THE APPLICABLE STANDARD | | | BUILDING CODES.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.101.1 AND FLA.STATUTE. | | | | | | CLEARLY SHOW TERMINATION POINT OF CON- | | | DENSATE DRAINS ON ROOF.DRAINS SHALL NOT | | | DISCHARGE WHERE THE EFFLUENT CAN DRAIN | | | INTO A STREET,ALLEY OR OTHER AREAS | | | THAT WOULD CREATE A NUISANCE /MENACE. | | | SMC SEC.304.8.3(3). | | | | | | SHT.P1-EYEWASH SHALL DRAIN TO SANITARY | | | NOT DISCHARGE ONTO GROUND.SPC SEC.301.4, | | | 301.11.1. |
|