Plan Review Notes
Plan Review Notes For Permit 00021256
Permit Number 00021256
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00*******CONTINUATION OF PLBG.COMMENTS****
 24)POT/SCULLERY SINKS SHALL BE STACKED
 AND VENTED PER SPC SEC.804.1.
  
 25)HEATER P& T LINE SHALL DISCHARGE TO
 AN OBSERVABLE POINT PER COUNTYWIDE AMEND
 MENTS TO SPC SEC.507.8.4.
  
 26)SUBMIT WATER PIPING/DRAINAGE DETAILS
 FOR ROTISSERIE AREA AND SUMP PUMP AT
 TRUCK DOCK.
  
 27)SIZE ALL SECTIONS OF THE COMPRESSED
 AIR SYSTEM.
  
 28)WATER FILTRATION SYSTEM SHALL BE NSF
 APPROVED PER SPC SEC.615.1,615.2.SUBMIT
 DATA.
  
 29)SHT.P-4-SIZE AND DESIGN OF GREASE
 TRAP SHALL BE APPROVED BY CITY OF WEST
 PALM BEACH UTILITIES.CONTACT R.COMPO AT
 (561)835-7423.
  
 30)SHT.P-3-DETAILS #8,11,ET.AL.-LOCATION
 OF FLOOR DRAINS SHALL COMPLY W/SPC SEC.
 409.4.1.2.