| Plan Review Notes For Permit 00021256 |
| Permit Number |
00021256 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: LOAD CALCULATIONS AT THE BOTTOM | | | OF EACH PANEL ARE NOT COMPLETE? PLEASE | | | SHOW ALL CONTIUOUS LOADS AT 125%. | | | LARGEST MOTORS/LIGHTING ETC. | | | | | | 2)NOTE: PLEASE SUBMIT FINAL LOAD CALC | | | FOR MAIN SERVICE. NEW EQUIPMENT/LOADS | | | ARE BEING ADDED TO EXISTING SERVICE. | | | | | | | | | 3)NOTE: SEE PANELBOARD 'HPM'. THIS IS | | | LISTING A 14,000 AIC RATING? PLEASE | | | CLARIFY. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 |
|