Plan Review Notes
Plan Review Notes For Permit 00021256
Permit Number 00021256
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: LOAD CALCULATIONS AT THE BOTTOM
 OF EACH PANEL ARE NOT COMPLETE? PLEASE
 SHOW ALL CONTIUOUS LOADS AT 125%.
 LARGEST MOTORS/LIGHTING ETC.
  
 2)NOTE: PLEASE SUBMIT FINAL LOAD CALC
 FOR MAIN SERVICE. NEW EQUIPMENT/LOADS
 ARE BEING ADDED TO EXISTING SERVICE.
  
  
 3)NOTE: SEE PANELBOARD 'HPM'. THIS IS
 LISTING A 14,000 AIC RATING? PLEASE
 CLARIFY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372