2001-01-08 00:00:00JOB SPEC.15050-SEC.3.02(I)-VERTICAL AND
 HORIZONTAL SPACING OF PIPE SUPPORTS
 SHALL COMPLY W/SPC SECS.310.2,310.3
 RESPECTIVELY.
  
 2)JOB SPEC.15400-SEC.2.01(D)-PIPING
 INSULATION SHALL COMPLY W/FLA.ENERGY
 CODE TABLE 4-11.
  
 3)JOB SPEC.15400-SEC.2.15-GREASE
 RECOVERY UNITS NOT PERMITTTED PER CITY
 ORDINANCE.
  
 4)JOB SPEC.15400-SEC.3.01(A)-SLOPE OF
 DRAINAGE PIPE SHALL COMPLY W/SPC SEC.
 705.2,705.3.9(SEE SHT.P1,NOTE #3 ALSO)
  
 5)SHT.CV1-THE CURRENT ADOPTED PLUMBING
 CODE IN THE CITY OF WEST PALM BEACH IS
 THE 1994 EDITION OF THE STANDARD
 PLUMBING,NOT 1997.
  
 6)THE MINIMUM NUMBER OF SANITARY FACIL-
 ITIES REQD.BY 1994 PLBG.CODE IS :
 MALES]-WATERCLOSETS-5
 -LAVATORIES_____5
 FEMALES]-WATER CLOSETS-9
 -LAVATORIES____9
 -DRINKING FOUNTAINS-4
 SEE SPC CODE SEC.407.1.3 & TABLE 407.
  
 7)ALL COMMON AND PUBLIC AREA TOILET
 ROOMS SHALL COMPLY W/FACBC SEC.4.1.3(11)
  
 8)SHT.A-4-TOP OF H.C.LAV.AFF SHALL BE
 34" PER FACBC SEC.4.19.2.
  
 9)SHT.A-5-DRINKING FOUNTAIN IN TMA SHALL
 BE H.C.ACCESSIBLE AND COMPLY W/FACBC
 SEC.4.1.3.(10)(A).
  
 10)TOILET ROOM IN TMA SHOWROOM SHALL BE
 HANDICAP ACCESSIBLE PER FACBC SEC.4.1.3.
 (11)
  
 11)SUBMIT WATER PIPING AND DRAINAGE
 DETAILS FOR RACK WASHER.
  
 12)WATER HEATER SHALL BE READILY ACCESS-
 IBLE.PROVIDE PERMANENT LADDER OR RE-
 LOCATE TO FLOOR.SPC 501.7.
  
 13)CLEARLY SHOW TYPE OF FINISH ON REST-
 ROOM WALLS.COMPLY W/SBC SEC.1204.2(NON-
 ABSORBENT TO A HEIGHT OF 4'.)
  
 14)SUBMIT MANUF.SHEETS FOR FILM PROCESS-
 OR AND SILVER RECOVERY UNIT.WASTE SHALL
 BE NEUTRALIZED PER SPC SEC.801.4.DATA
 SHOWING ESTIMATED PH OF EFFLUENT SHALL
 BE SUBMITTED FOR REVIEW.
  
 15)SINK IN EMPLOYEE LOUNGE SHALL BE H.C.
 ACCESSIBLE AND COMPLY W/FACBC SEC.4.24.1
 THRU 4.24.7.
  
 16)SUBMIT WASTE AND WATER RISER FOR SINK
 IN EMPLOYEE LOUNGE ,RM.112.LINE SHALL
 DRAIN TO SANITARY PER SPC 1004.3.
  
 17)WATER SUPPLY CONTROL FOR ALL AREAS
 SHALL COMPLY W/SPC SEC.610.4.1.,610.4.2.
  
 18)SIZE ALL WASTE,VENT AND WATER LINES
 ON THE RISER DIAGRAMS.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 19)HAND SINKS,SERVICE SINKS,FLOOR DRAINS
 AND SIMILAR FIXTURES IN THE FOOD/SNACK
 BAR AREAS SHALL DISCHARGE THROUGH THE
 GREASE INTERCEPTOR PER SPC SEC.1004.4.
  
 20)INDIRECT WASTE LINES SHALL COMPLY W/
 SPC SEC.805.1.1,805.2.
  
 21)FLOOR DRAINS NOT SUPPLIED W/INDIRECT
 WASTES SHALL BE EQUIPPED W/TRAP PRIMERS
 PER SPC SEC.409.4.1.1.
  
 22)SUBMIT COMPLETE GAS DRAWING FOR
 REVIEW.SHOW MOST REMOTE OUTLET,CUT
 SECTIONS OF PIPE,BTU LOAD OF EACH PIECE
 OF EQUIP.ALL EQUIPMENT SHALL BE LISTED/
 APPROVED PER SGC SEC.402.1 AND NFPA 54.
 SUBMIT MANUF. SHEETS FOR ALL GAS EQUIP.
  
 23)SUMPS SHALL COMPLY W/SPC SEC.717.SUB-
 MIT DETAILS ON SUMP CONSTRUCTION,PUMPS
 ETSC.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.