| 2001-01-08 00:00:00 | JOB SPEC.15050-SEC.3.02(I)-VERTICAL AND |
| | HORIZONTAL SPACING OF PIPE SUPPORTS |
| | SHALL COMPLY W/SPC SECS.310.2,310.3 |
| | RESPECTIVELY. |
| | |
| | 2)JOB SPEC.15400-SEC.2.01(D)-PIPING |
| | INSULATION SHALL COMPLY W/FLA.ENERGY |
| | CODE TABLE 4-11. |
| | |
| | 3)JOB SPEC.15400-SEC.2.15-GREASE |
| | RECOVERY UNITS NOT PERMITTTED PER CITY |
| | ORDINANCE. |
| | |
| | 4)JOB SPEC.15400-SEC.3.01(A)-SLOPE OF |
| | DRAINAGE PIPE SHALL COMPLY W/SPC SEC. |
| | 705.2,705.3.9(SEE SHT.P1,NOTE #3 ALSO) |
| | |
| | 5)SHT.CV1-THE CURRENT ADOPTED PLUMBING |
| | CODE IN THE CITY OF WEST PALM BEACH IS |
| | THE 1994 EDITION OF THE STANDARD |
| | PLUMBING,NOT 1997. |
| | |
| | 6)THE MINIMUM NUMBER OF SANITARY FACIL- |
| | ITIES REQD.BY 1994 PLBG.CODE IS : |
| | MALES]-WATERCLOSETS-5 |
| | -LAVATORIES_____5 |
| | FEMALES]-WATER CLOSETS-9 |
| | -LAVATORIES____9 |
| | -DRINKING FOUNTAINS-4 |
| | SEE SPC CODE SEC.407.1.3 & TABLE 407. |
| | |
| | 7)ALL COMMON AND PUBLIC AREA TOILET |
| | ROOMS SHALL COMPLY W/FACBC SEC.4.1.3(11) |
| | |
| | 8)SHT.A-4-TOP OF H.C.LAV.AFF SHALL BE |
| | 34" PER FACBC SEC.4.19.2. |
| | |
| | 9)SHT.A-5-DRINKING FOUNTAIN IN TMA SHALL |
| | BE H.C.ACCESSIBLE AND COMPLY W/FACBC |
| | SEC.4.1.3.(10)(A). |
| | |
| | 10)TOILET ROOM IN TMA SHOWROOM SHALL BE |
| | HANDICAP ACCESSIBLE PER FACBC SEC.4.1.3. |
| | (11) |
| | |
| | 11)SUBMIT WATER PIPING AND DRAINAGE |
| | DETAILS FOR RACK WASHER. |
| | |
| | 12)WATER HEATER SHALL BE READILY ACCESS- |
| | IBLE.PROVIDE PERMANENT LADDER OR RE- |
| | LOCATE TO FLOOR.SPC 501.7. |
| | |
| | 13)CLEARLY SHOW TYPE OF FINISH ON REST- |
| | ROOM WALLS.COMPLY W/SBC SEC.1204.2(NON- |
| | ABSORBENT TO A HEIGHT OF 4'.) |
| | |
| | 14)SUBMIT MANUF.SHEETS FOR FILM PROCESS- |
| | OR AND SILVER RECOVERY UNIT.WASTE SHALL |
| | BE NEUTRALIZED PER SPC SEC.801.4.DATA |
| | SHOWING ESTIMATED PH OF EFFLUENT SHALL |
| | BE SUBMITTED FOR REVIEW. |
| | |
| | 15)SINK IN EMPLOYEE LOUNGE SHALL BE H.C. |
| | ACCESSIBLE AND COMPLY W/FACBC SEC.4.24.1 |
| | THRU 4.24.7. |
| | |
| | 16)SUBMIT WASTE AND WATER RISER FOR SINK |
| | IN EMPLOYEE LOUNGE ,RM.112.LINE SHALL |
| | DRAIN TO SANITARY PER SPC 1004.3. |
| | |
| | 17)WATER SUPPLY CONTROL FOR ALL AREAS |
| | SHALL COMPLY W/SPC SEC.610.4.1.,610.4.2. |
| | |
| | 18)SIZE ALL WASTE,VENT AND WATER LINES |
| | ON THE RISER DIAGRAMS.COUNTYWIDE AMEND- |
| | MENTS TO SPC SEC.104.2.1. |
| | |
| | 19)HAND SINKS,SERVICE SINKS,FLOOR DRAINS |
| | AND SIMILAR FIXTURES IN THE FOOD/SNACK |
| | BAR AREAS SHALL DISCHARGE THROUGH THE |
| | GREASE INTERCEPTOR PER SPC SEC.1004.4. |
| | |
| | 20)INDIRECT WASTE LINES SHALL COMPLY W/ |
| | SPC SEC.805.1.1,805.2. |
| | |
| | 21)FLOOR DRAINS NOT SUPPLIED W/INDIRECT |
| | WASTES SHALL BE EQUIPPED W/TRAP PRIMERS |
| | PER SPC SEC.409.4.1.1. |
| | |
| | 22)SUBMIT COMPLETE GAS DRAWING FOR |
| | REVIEW.SHOW MOST REMOTE OUTLET,CUT |
| | SECTIONS OF PIPE,BTU LOAD OF EACH PIECE |
| | OF EQUIP.ALL EQUIPMENT SHALL BE LISTED/ |
| | APPROVED PER SGC SEC.402.1 AND NFPA 54. |
| | SUBMIT MANUF. SHEETS FOR ALL GAS EQUIP. |
| | |
| | 23)SUMPS SHALL COMPLY W/SPC SEC.717.SUB- |
| | MIT DETAILS ON SUMP CONSTRUCTION,PUMPS |
| | ETSC.COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 104.2.1. |