| Plan Review Notes For Permit 00021244 |
| Permit Number |
00021244 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SIZING OF GAS SYSTEM SHALL COMPLY W/SGC | | | TABLES 305.4(A),305.4(F).3/4" SUPLLY | | | CANNOT HANDLE 153 CFH @ 80'. | | | | | | INDICATE MANUF.OF CSST ON PLANS AND SHOW | | | PROPER EHD OF CSST PER TABLE 305.4(F)OR | | | SUBMIT SIZING TABLE FROM MANUF.TO ENSURE | | | CODE COMPLIANCE W/SGC.(CSST TO WATER | | | HEATER AND DRYER IS UNDER SIZED.) |
|