Date Text
2001-01-08 00:00:00FLOOR DRAIN CANNOT BE LOCATED UNDER SINK
 INLET SHALL BE IN FULL VIEW AT ALL TIMES
 SPC SEC.409.4.1.2.
  
 SUBMIT A WATER RISER FOR REVIEW.WATER
 SUPPLY CONTROL SHALL COMPLY W/SPC SEC.
 610.4.1.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PROVIDE PERMANENT ACCESS LADDER OR
 RELOCATE EWH TO FLOOR.SPC 501.7.
  
 ADDENDUM PLBG.SHEETS SHALL BE SIGNED AND
 SEALED PER FLA.STATUTE & COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.3.
  
 *************PROVISO********************
 SUBMIT REVISIONS FOR ABOVE ITEMS PRIOR
 TO ROUGH PLUMBING INSP.