| 2001-01-08 00:00:00 | FLOOR DRAIN CANNOT BE LOCATED UNDER SINK | | | INLET SHALL BE IN FULL VIEW AT ALL TIMES | | | SPC SEC.409.4.1.2. | | | | | | SUBMIT A WATER RISER FOR REVIEW.WATER | | | SUPPLY CONTROL SHALL COMPLY W/SPC SEC. | | | 610.4.1. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PROVIDE PERMANENT ACCESS LADDER OR | | | RELOCATE EWH TO FLOOR.SPC 501.7. | | | | | | ADDENDUM PLBG.SHEETS SHALL BE SIGNED AND | | | SEALED PER FLA.STATUTE & COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.3. | | | | | | *************PROVISO******************** | | | SUBMIT REVISIONS FOR ABOVE ITEMS PRIOR | | | TO ROUGH PLUMBING INSP. |
|