Plan Review Notes
Plan Review Notes For Permit 00021185
Permit Number 00021185
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW INDETAIL THE GROUND-
 -ING ELECTRODE SYSTEM AT GARAGE. TO GRND
 ROD AND COLD WATER PIPE. 250-81
  
 2)NOTE: PLEASE NOTE THAT YOU HAVE TO
 GROUP MAINS AS PER 230-72 AT HOUSE.
 YOU SHOW FEED FOR GARAGE COMING OUT OF
 METER CAN. THIS CANNOT BE DONE. ALSO
 SUBMIT LOAD CALCULATION ON MAIN HOUSE
 ELECTRIC IF YOU ARE FEEDING ON EXISTING
 RISER/OR PANEL.
  
 3)NOTE:ALSO 3-2/0`S TO GARAGE???
  
 4)NOTE:ALSO 5KW A/C UNIT DOES NOT REQ`
 50AMP BRKR OR 3-#6 CONDUCTORS. #10 EQUIP
 MENT GROUND.NEED TO SHOW COMPLETE DETAIL
 ON A/C SYSTEM BEING INSTALLED IN WALL
 OF THE SMALL ROOM.THIS WIRING CAN NOT
 BE INSTALLED. MUST BE WIRING FOR RATED
 A/C UNIT. 3-#10`S. NO ELEC.MAY BE
 INSTALLED THAT MAY BE CHANGED FOR FUTURE
 COOKING.ALSO, 2 POLE 50 IS TOO LARGE FOR
 UNIT.
  
 5)NOTE:PLEASE INCLUDE BATH ON PANEL
 SCHEDULE. AS REQ`D BY 210-52D AND 210-11
 -C-3.
  
 NOTE THAT ZONING AS NOTED , NO KITCHEN
 WILL BE PERMITTED IN THIS STRUCTURE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT
 8372