| 2001-01-08 00:00:00 | *************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SHOW INDETAIL THE GROUND- |
| | -ING ELECTRODE SYSTEM AT GARAGE. TO GRND |
| | ROD AND COLD WATER PIPE. 250-81 |
| | |
| | 2)NOTE: PLEASE NOTE THAT YOU HAVE TO |
| | GROUP MAINS AS PER 230-72 AT HOUSE. |
| | YOU SHOW FEED FOR GARAGE COMING OUT OF |
| | METER CAN. THIS CANNOT BE DONE. ALSO |
| | SUBMIT LOAD CALCULATION ON MAIN HOUSE |
| | ELECTRIC IF YOU ARE FEEDING ON EXISTING |
| | RISER/OR PANEL. |
| | |
| | 3)NOTE:ALSO 3-2/0`S TO GARAGE??? |
| | |
| | 4)NOTE:ALSO 5KW A/C UNIT DOES NOT REQ` |
| | 50AMP BRKR OR 3-#6 CONDUCTORS. #10 EQUIP |
| | MENT GROUND.NEED TO SHOW COMPLETE DETAIL |
| | ON A/C SYSTEM BEING INSTALLED IN WALL |
| | OF THE SMALL ROOM.THIS WIRING CAN NOT |
| | BE INSTALLED. MUST BE WIRING FOR RATED |
| | A/C UNIT. 3-#10`S. NO ELEC.MAY BE |
| | INSTALLED THAT MAY BE CHANGED FOR FUTURE |
| | COOKING.ALSO, 2 POLE 50 IS TOO LARGE FOR |
| | UNIT. |
| | |
| | 5)NOTE:PLEASE INCLUDE BATH ON PANEL |
| | SCHEDULE. AS REQ`D BY 210-52D AND 210-11 |
| | -C-3. |
| | |
| | NOTE THAT ZONING AS NOTED , NO KITCHEN |
| | WILL BE PERMITTED IN THIS STRUCTURE. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW AND APPROVAL. IF THERE ARE |
| | ANY QUESTIONS PLEASE CALL 659-8096 EXT |
| | 8372 |