| Plan Review Notes For Permit 00021175 |
| Permit Number |
00021175 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SHOW SMOKE DETECTORS | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | AS REEQ`D BY NFPA-72 2-2.1.1.1 INCLUDING | | | ROOMS THAT MAY BE CONVERTED TO SLEEPING | | | ROOMS. | | | | | | 2)NOTE:PLEASE SHOW RECEPT REQ`D BY ART; | | | 210-63 | | | | | | 3)NOTE:NO EQUIPMENT GROUND IS TO BE | | | INSTALLED FROM METER TO FIRST MEANS OF | | | DISCONNECT. | | | | | | 4)NOTE:PLEASE INCLUDE BATH(S) CIRCUT(S) | | | ON PANEL SCHEDULE.AS REQ`D BY 210-11-C-3 | | | | | | 5)NOTE: NEED TO IN AIC RATING OF MAIN | | | AS REQ`D BY 110-9/215-5 MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT. | | | | | | 6)NOTE:SMALL APPLIANCE CIRCUTS REQ`D BY | | | 210-11-C-1 #12 AND 20AMP X TWO,1500VA | | | | | | 7)NOTE: PLEASE INCLUDE COLD WATER PIPE | | | AS PART OF GROUNDING ELEC. SYSTEM AS | | | PER 250-81 | | | | | | 8)NOTE:PLEASE CHECK THE HEAT STRIP BEING | | | INSTALLED?? THIS 5KW SEEMS LIKE IT WILL | | | BE TOO SMALL FOR 1200 SQ FT. | | | | | | PLEASE SUBMIT FOR REVIEW AND APPROVAL | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|