Plan Review Notes
Plan Review Notes For Permit 00021175
Permit Number 00021175
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW SMOKE DETECTORS
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 AS REEQ`D BY NFPA-72 2-2.1.1.1 INCLUDING
 ROOMS THAT MAY BE CONVERTED TO SLEEPING
 ROOMS.
  
 2)NOTE:PLEASE SHOW RECEPT REQ`D BY ART;
 210-63
  
 3)NOTE:NO EQUIPMENT GROUND IS TO BE
 INSTALLED FROM METER TO FIRST MEANS OF
 DISCONNECT.
  
 4)NOTE:PLEASE INCLUDE BATH(S) CIRCUT(S)
 ON PANEL SCHEDULE.AS REQ`D BY 210-11-C-3
  
 5)NOTE: NEED TO IN AIC RATING OF MAIN
 AS REQ`D BY 110-9/215-5 MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.
  
 6)NOTE:SMALL APPLIANCE CIRCUTS REQ`D BY
 210-11-C-1 #12 AND 20AMP X TWO,1500VA
  
 7)NOTE: PLEASE INCLUDE COLD WATER PIPE
 AS PART OF GROUNDING ELEC. SYSTEM AS
 PER 250-81
  
 8)NOTE:PLEASE CHECK THE HEAT STRIP BEING
 INSTALLED?? THIS 5KW SEEMS LIKE IT WILL
 BE TOO SMALL FOR 1200 SQ FT.
  
 PLEASE SUBMIT FOR REVIEW AND APPROVAL
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372