2001-01-08 00:00:00*************** PROVISO ****************
  
 1)NOTE: PLEASE INDICATE ON PLANS THAT
 ALL UF CABLES ARE TO BE PROTECTED
 ACCORDING TO ART;300-5-D
  
 2)NOTE: PLEASE SUBMIT PLANS SHOWING ALL
 WIRE SIZES FROM MAIN PANEL TO JB`S AND
 GOING ON TO OTHER ELEC. JUNCTION BOXES.
 KEE[ IN MIND THE VOLYAGE DROP FROM MAIN
 PANEL. YOUR SCALE SHOWS 1" = 40'.
  
 PLEASE SUMIT THE ABOVE INFORMATION
 BEFORE FIRST GROUND ROUGH IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372