Plan Review Notes For Permit 00021153
Permit Number 00021153
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE:NEED TO SUBMIT ALL AIC RATINGS OF
 MAINS.110-9/215-5 MAINS ARE TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT.
  
 2)NOTE:YOU SHOW EQUIPMENT GROUNDING
 CONDUCTORS FROM METER TO MAIN DISC? ONLY
 AFTER FIRST MEANS OF DISCONNECT.
  
 3)NOTE:YOU NEED TO SUBMIT NEW LOAD
 CALCUALTIONS FOR EXISTING HOUSE SERVICE
 PER 220-3-C-1
  
 4)NOTE:PLEASE CHECK PANEL SCHEDULES. ALL
 BATH CIRCUTS PER 210-11-C-3 20AMP #12
  
 5)NOTE:PLEASE SHOW COMPLETE GROUNDING
 ELECTRODE SYSTEM FOR THE NEW MAIN HOUSE
 SERVICE.
  
 6)NOTE:PLEASE NOTE ALL THE REQ`MENTS FOR
 SMOKE DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS!! THIS NEEDSTOINCLUDE
 ALL SD`S IN COMMON AREAS FOR TWO STORY.
 NFPA-72 2-2.1.1.1
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372