| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** PROVISO ***************** | | | | | | 1)NOTE:NEED TO SUBMIT ALL AIC RATINGS OF | | | MAINS.110-9/215-5 MAINS ARE TO BE RATED | | | FOR THE AVAILABLE FAULT CURRENT. | | | | | | 2)NOTE:YOU SHOW EQUIPMENT GROUNDING | | | CONDUCTORS FROM METER TO MAIN DISC? ONLY | | | AFTER FIRST MEANS OF DISCONNECT. | | | | | | 3)NOTE:YOU NEED TO SUBMIT NEW LOAD | | | CALCUALTIONS FOR EXISTING HOUSE SERVICE | | | PER 220-3-C-1 | | | | | | 4)NOTE:PLEASE CHECK PANEL SCHEDULES. ALL | | | BATH CIRCUTS PER 210-11-C-3 20AMP #12 | | | | | | 5)NOTE:PLEASE SHOW COMPLETE GROUNDING | | | ELECTRODE SYSTEM FOR THE NEW MAIN HOUSE | | | SERVICE. | | | | | | 6)NOTE:PLEASE NOTE ALL THE REQ`MENTS FOR | | | SMOKE DETECTORS INSIDE AND OUTSIDE ALL | | | SLEEPING ROOMS!! THIS NEEDSTOINCLUDE | | | ALL SD`S IN COMMON AREAS FOR TWO STORY. | | | NFPA-72 2-2.1.1.1 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN.IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|