| Plan Review Notes For Permit 00021132 |
| Permit Number |
00021132 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE; NEED TO SUBMIT SHOWING COMPLETE | | | LOAD CALCULATIONS SHOWING ALL COTINUOUS | | | LOAD AT 125% (LIGHTING ETC ) | | | | | | 2)NOTE: MAIN PANEL SCHEDULE SHOWS 150 | | | GOING TO ROOF TOP A/C ? OR IS THAT THE | | | MAIN FOR THE OTHER PANEL? PLEASE CLARIFY | | | | | | 3)NOTE: PLEASE PROVIDE ALL AIC RATINGS | | | OF EQUIPMENT MAINS/ BRANCH PANELS ALSO. | | | MAINS MUST BE RATED FOR THE AVAILBALE | | | FAULT CURRENT AS PER 110-9/110-10 | | | | | | 4)NOTE: ALL OUTLETS IN BATHS MUST BE | | | GFI/GFI PROTECTED AS PER 210-8-B IN OTHR | | | THAN DWELLING UNITS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS CALL | | | 659-8096 EXT 8372 |
|