| Plan Review Notes For Permit 00021105 |
| Permit Number |
00021105 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE:PLEASE SEPARATE BOTH PANEL SCHED. | | | HAVE THEM SHOWN AS TWO 42 CIRCUT PANELS | | | AS REQ`ED BY 384-15 AND 215-5 | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATION | | | AND SHOWING THE CALCULATION. PLEASE | | | SHOW CONTINUOUS LOADS AT 125% AND ANY | | | OTHER LOADS THAT MAY BE CONTINUOUS, | | | | | | 3)NOTE: OUTLET SPACING TO MEET LOCAL | | | CODE. 210-50 OFFICE AREA TO HAVE OUTLET | | | EVERY 12` OF WALL.TO INCLUDE ALL OF | | | LOBBY AREA. | | | | | | 4)NOTE: SHOW LOAD CALCULATION ON TRACK | | | LIGHTING. AS REQ`D BY ART 220 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS CALL | | | 659-8096 EXT 8372 |
|