| Plan Review Notes For Permit 00021020 |
| Permit Number |
00021020 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | LOCATION OF PLUMBING FIXTURES ON | | | SANITARY RISER SHALL CORRELATE W/FLOOR | | | PLAN AND RISER SHALL COMPLY W/STANDARD | | | PLBG.CODE. | | | A)MIN.SIZE OF PIPING U/G SHALL BE 2" PER | | | SPC SEC.714.4. | | | B)WATER CLOSETS AND TUBS IN BATHS 2 & 3 | | | NOT PROPERLY VENTED.SPC SEC.901.2. | | | C)REVISE KIT. SINK DRAIN AND VENT TO | | | COMPLY W/SPC SEC.901.2,905.7,908.2. |
|