Plan Review Notes
Plan Review Notes For Permit 00021020
Permit Number 00021020
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING OF
 EQUIPMENT MAINS. MAINS ARE TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT. 110-9
 215-5
  
 2)NOTE: YOU SHOW GROUNDING ELECTRODE
 CONDUCTOR GOING TO CWP OR BLDG.STEEL.
 BOTH MUST BE A PART OF THE GROUNDING
 ELECTRODE SYSTEM AS PER 250-50 PLEASE
 SHOW ON RISER DIAGRAM.215-5
  
 3)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUT(S) AS PER 210-11-C-3
  
 4)NOTE: SHOW LIGHT AS REQ`D BY 210-70-
 A-3
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE
 ARE ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372