| Plan Review Notes For Permit 00021007 |
| Permit Number |
00021007 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | LOCATION OF PLUMBING FIXTURES ON RISER | | | SHALL CORRELATE W/FLOOR PLAN.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | SANITARY DOESN'T COMPLY W/ SPC. | | | A)WATER CLOSETS AND SHOWERS NOT PROPERLY | | | VENTED.SPC 901.2,913.2. | | | B)FIXTURE BRANCHES AND WATER CLOSETS NOT | | | PERMITTED ON WET VENTS.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.911.1.1 | | | C)LAV AND KIT.SINK NOT VENTED.SPC 901.2. | | | D)MIN.SIZE DRAIN U/G SHALL BE 2" PER | | | SPC SEC.714.4. |
|