2001-01-08 00:00:00LOCATION OF PLUMBING FIXTURES ON RISER
 SHALL CORRELATE W/FLOOR PLAN.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 SANITARY DOESN'T COMPLY W/ SPC.
 A)WATER CLOSETS AND SHOWERS NOT PROPERLY
 VENTED.SPC 901.2,913.2.
 B)FIXTURE BRANCHES AND WATER CLOSETS NOT
 PERMITTED ON WET VENTS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1
 C)LAV AND KIT.SINK NOT VENTED.SPC 901.2.
 D)MIN.SIZE DRAIN U/G SHALL BE 2" PER
 SPC SEC.714.4.