| Plan Review Notes For Permit 00021007 |
| Permit Number |
00021007 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATING | | | OF EQUIPMENT MAINS. MAINS MUST BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110-9/215-5 PLEASE LIST ON PANEL | | | SCHEDULE. | | | | | | 2)NOTE: PLEASE SHOW ON RISER DIAGRAM THE | | | GROUNDING ELECTRODE CONDUCTOR GOING TO | | | BLDG.STEEL AS REQ`D BY 250-50 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEWAND APPROVAL. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|