| Plan Review Notes For Permit 00020987 |
| Permit Number |
00020987 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** PROVISO *************** | | | | | | 1)NOTE: NEED TO SHOW THE SIZE OF THE | | | EXISTING SERVICE. NEED TO SUBMIT NEW | | | LOAD CALCULATION TO INCLUDE NEW A/C | | | LOAD BEINGADDED. | | | | | | 2)NOTE: AS REQ`D BY 210-52D/210-11-C-3 | | | BATH CIRCUT TO BE DEDICATED. | | | | | | 3)NOTE: AS PER 110-16 NOTE CLEARENCE FOR | | | AHU. | | | | | | 4)NOTE: AS REQ`D BY NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDEALL SLEEPING ROOMS. | | | | | | PLEASE SUBMIT FOR REVIEW AND APPROVAL | | | BEFORE ROUGH INSPECTION. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 X | | | 8372 |
|