Plan Review Notes
Plan Review Notes For Permit 00020965
Permit Number 00020965
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE:NEED TO SUBMIT AIC RATINGS OF ALL
 EQUIPMENT MAINS. MAINS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT AS REQ`D BY
 110-9/110-10 OF THE NEC. SHOW ON EACH
 PANEL.
  
 2)NOTE:MISSING LIGHTING IN FIRST FLOOR
 BATHROOMS. AS REQ`D BY 210-70
  
 3)NOTE:PLEASE INDICATE THE SWITCHES AS
 3-WAY IF THIS IS THE CASE.
  
 4)NOTE:PLEASE INDICATE ALL BRANCH CIRCUT
 #`S ON PLANS FOR LIGHTING AND OUTLETS.
  
 5)NOTE:PLEASE NOTE THAT OUTLETS ARE REQ`
 -D FOR SHOW WINDOWS AS PER 210-62.
 THEY MUST BE DIRECTLY ABOVE WINDOW.
  
 6)NOTE:PLEASE SHOW LOAD CALCULATIONS
 SHOWING THE SEPARATE LOAD REQ`D FOR
 TRACK LIGHTING AND SHOW WINDOWS. AS PER
 220-12 A&B
 ALSO PLEASE SHOW LIGHTING LOADS AT 125%
 FOR CONTINUOUS DUTY. 3 OR MORE HOURS.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 ANY INSPECTIONS ARE CALLED IN. IF THERE
 ARE ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372