| 2001-01-08 00:00:00 | **************** UNSAT ***************** |
| | |
| | 1)NOTE: LOAD CALCULATION STILL NEEDS TO |
| | BE RE-DONE. MCC-S IS STILL SHOWING LOAD |
| | FROM BEFORE WHEN DIMMER PACK LOADS |
| | WERE NOT FIGURED AT 125%. THIS WILL |
| | CHANGE LOAD CALCUALTION SHOWN ON MCC-S |
| | |
| | 2)NOTE: PLEASE CAHNGE ON RISER.STILL |
| | SHOWS 293A |
| | |
| | 3)NOTE: PLEASE CORRECT LOAD CALCULATION |
| | FOR MCC-S. CONNECTED LOAD SHOWN AT 175?? |
| | WHEN CONNECTED LOAD FOR MOTORS ARE 189A |
| | WHICH IS WHAT YOU SHOW FURTHER DOWN. |
| | 125% IS FIGURED FOR LARGEST MOTOR ONLY?? |
| | WHERE IS THE 58AMPS COMING FROM. |
| | |
| | 4)NOTE: PLEASE INCLUDE A NOTEON PLANS |
| | FOR CLASS A PROTECTION FOR PUMPS IN |
| | FOUNTAIN. PLEASE NOTE FOR SETTING OF |
| | GFI PROTECTION ON VFD`S LIKE YOU HAVE |
| | FOR LIGHTING. |
| | |
| | 5)NOTE: PLEASE MAKE THE CORRECTION FOR |
| | THE AIC RATING OF MAIN ON SWITCHBOARD-- |
| | "PB". I HAVE SPOKEN TO ELECTRICAL |
| | CONTRACTOR AND IT IS MY UNDERSTANDING |
| | THAT THE MAIN IS GOING TO BE INCREASED |
| | FOR THE AVAILABLE FAULT CURRENT?? |
| | PLEASE VERIFY AND SHOW THE RATING OF |
| | MAIN BEING INSTALLED.215-5 |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. WE ARE STILL WAITING FOR |
| | SHOP DRAWINGS/SPEC BOOKS??? PLEASE |
| | SUBMIT WITH PLANS. IF THERE ARE ANY |
| | QUESTIONS PLEASE CALL 561-659-8096 EXT - |
| | 8372 |