| 2001-01-08 00:00:00 | **************** UNSAT ***************** |
| | |
| | PLEASE NOTE THAT SOME OF THE ORIGINAL |
| | COMMENTS WERENOT ADDRESSED. |
| | |
| | 1)NOTE: STILL NEED TO SEE W-5.7 FOR THE |
| | LOAD THAT YOUARE SHOWING FOR LIGHTING. |
| | YOU ARE SHOWWING LOAD FOR DIMMER PACK 'B |
| | AT 234 AMPS. THIS IS CORRECT BUT ON W5.4 |
| | YOU SHOW LOAD AT 200 AMPS??? |
| | PLEASE CORRECT. |
| | |
| | 2)NOTE:ALSO, THE FEEDER WIRES FOR BOTH |
| | DIMMER PACKS SHOWN ARE NOT RATED FOR THE |
| | LOADS. |
| | PLEASE CHANGE DTO CORRECT WIRE SIZE AS |
| | PER 310-16.. |
| | |
| | 3)NOTE : SINCE THE LOAD SHOWN ON W5.4 |
| | FOR DIMMER 'B' DOES NOT MATCH CORRECT |
| | LOAD SHOWN ON W5.7. THE TOTAL LOAD FOR |
| | MCC-S WILL HAVE TO CHANGE ALSO. |
| | |
| | 4)NOTE: AS PREVIOUS NOTES STATES, PLEASE |
| | SHOW THE LOAD FOR MCC-S WITH THE ADDED |
| | 25% FOR LARGEST MOTOR.PLEASE SHOW FIGS. |
| | |
| | 5)NOTE: YOU ARE SHOWING THE AIC RATING |
| | FOR THE PANEL SWITCHBOARD 'PB' AS BEING |
| | 10,000 AIC. PLEASE SUBMIT FAULT CURRENT |
| | CALCULATIONS FOR THIS. YOU SHOW A 300KVA |
| | TRANSFORMER NEXT TO PNAEL 'PB'. 110-9 |
| | 215-5 |
| | |
| | **************************************** |
| | |
| | 1)NOTE: AFTER REVIEWING SPECS FOR THE |
| | INSTALLATION OF THE "BENDER" GFI MODULES |
| | ANY MODULES INSTALLED MUST MEET THE |
| | UL 943 CLASS'A' WITH PROTECTION SET AT |
| | 6MA OR LESS FOR PERSONNEL PROTECTION. |
| | AS PER 680-51. |
| | |
| | 2)NOTE: ON W4.5 ALL FITTINGS USED FOR |
| | GROUNDING/BONDING IN AND ABOUT FOUNTAIN |
| | ARE TO BE LISTED FOR USE AS DIRECT |
| | BURIAL AND CONCRETE ENCASEMENT. |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 561-659-8096 EXT 8372 |