| 2001-01-08 00:00:00 | PLANS SHALL BE REVIEWED AND APPROVED BY |
| | THE DEPT.OF BUSINESS AND PROFESSIONAL |
| | REGULATION PRIOR TO REVIEW BY THIS DEPT. |
| | PER COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.101.4.7. |
| | |
| | CLARIFY TYPE OF OCCUPANCY ON TITLE SHEET |
| | THERE IS NO "A-3"OCCUPANCY IN THE SBC. |
| | SBC 304.2.1. |
| | |
| | SUBMIT OCCUPANT LOAD BASED ON HABITABLE |
| | FLOOR SPACE PER SPC SEC.407.1.3. |
| | PLANS NOTE OCCUPANT LOAD AS 416 PERSONS- |
| | AND DO NOT COMPLY W/SPC TABLE 407 OR FLA |
| | STATUTE 553.141.FOR MIN.FIXTURE REQS. |
| | |
| | PLANS SHALL BEAR THE CITY PLACE LANDLORD |
| | APPROVAL STAMP PRIOR TO APPROVAL FROM |
| | THIS DEPT. |
| | |
| | SHOW INSIDE CLEAR DIMENSIONS (LXW) OF |
| | ACCESSIBLE TOILET ROOMS AND STALLS. |
| | COMPLY W/FACBC SECS.4.16,4.17,FIGURES#28 |
| | & #30.TOILETS TO BE 18"FROM WALL,NOT 19" |
| | |
| | SHT.P-1-(INSULATION TABLE FOR WATER |
| | PIPING )-INSULATION THICKNESS FOR PIPING |
| | SHALL COMPLY W/FLA.ENERGY CODE TABLE |
| | 4-11.(FOR PIPING 1" AND LESS MIN.THICK- |
| | NESS SHALL BE 1") |
| | |
| | WATER SUPPLY CONTROL SHALL COMPLY W/ |
| | SPC 610.4.1(THERE ARE FIXTURES THAT |
| | CANNOT BE ISOLATED W/O SHUTTING DOWN |
| | ENTIRE SYSTEM.REVIEW WATER RISER AND |
| | COMPLY.SEE SERVICE STATION ,BAKERY,2ND |
| | FLR.TOILET ROOMS,ETC.) |
| | |
| | FIXTURE UNIT LOAD FOR SANITARY AND |
| | GREASY WASTE SYSTEM SHALL COMPLY W/SPC |
| | TABLES 713.1,713.2.REVISE FIXTURE UNIT |
| | LOAD. |
| | |
| | SUBMIT DETAILS FOR GAS VENT ON WATER |
| | HEATER.INDICATE TYPE OF VENT,HEIGHT,ETC. |
| | COMPLY W/SGC SECS.605.3,608.3. |
| | |
| | SUBMIT CALCULATIONS FOR COMBUSTION AIR |
| | FOR GAS APPLIANCES.COMPLY W/SGC SEC. |
| | 402.4.4. |
| | |
| | INSTALLATION OF WATER HEATER SHALL |
| | COMPLY W/SGC SEC.405.1.1.SUBMIT MANUF. |
| | SHEETS FOR WATER HEATER AND ALL OTHER |
| | GAS EQUIPMENT.SGC SEC.402.1. |
| | |
| | ALL GAS VALVES SHALL BE READILY ACCESS- |
| | IBLE PER SGC 403.1.2.PLANS SHOW VALVES |
| | BEHIND EQUIPMENT. |
| | |
| | SHT.K-2.1-NO WATER ABOVE 140 DEGREES |
| | SHALL DISCHARGE INTO THE DRAINAGE SYSTEM |
| | PER SPC SEC.807.3.(SEE WATER HEATER NOTE |
| | |
| | SHT.P-8-CLARIFY BTU LOAD OF GAS WATER |
| | HEATER.PLANS NOTE 1800 & 1852 CFH. |
| | |
| | ELEVATOR SUMP DRAIN IS NOT SHOWN ON |
| | WASTE PIPING RISER.DISCHARGE SHALL BE TO |
| | SANITARY SYSTEM NOT GREASY WASTE.IF |
| | ELEVATOR IS HYDRAULIC,DRAIN SHALL FIRST |
| | PASS THRU AN OIL INTERCEPTOR PRIOR TO |
| | DISCHARGE TO SANITARY SYSTEM PER SPC |
| | SEC.1004.1,1004.5,1004.8. |
| | |
| | A UNION IS REQD.DOWNSTREAM OF ELECTRONIC |
| | GAS VALVE TO ALLOW FOR REMOVAL/REPLACE- |
| | MENT.NFPA 54 SEC.5.5.4. |
| | |
| | GAS SYSTEM IS UNDERSIZED FOR THE TOTAL |
| | BTU LOAD AND DISTANCE FROM POINT OF |
| | DELIVERY PER SGC TABLE 305.4(A). |
| | |