| 2001-01-08 00:00:00 | |
| | ALL BATHROOMS IN THE COVERED DWELLING |
| | UNIT SHALL COMPLY W/THE PROVISIONS OF |
| | THE FAIR HOUSING ACT 24 CFR 100.205(C) |
| | (3)(IV)REQ.#7(2) PARAGRAPH (A) OR (B). |
| | CLEAR FLOOR SPACE SHALL BE PROVIDED AT |
| | FIXTURES TO ALLOW A PERSON IN A WHEEL- |
| | CHAIR OR OTHER MOBILITY AID USE OF THE |
| | FIXTURES.CLEAR FLOOR SPACE SHALL BE |
| | SHOWN ON THE PLANS AND DESIGNATE WHICH |
| | OPTION OF REQUIREMENT #7(A OR B)IS BEING |
| | USED. |
| | |
| | SHT.AP-A7.04-WOOD BACKING FOR GRAB BARS |
| | ON LONG WALL OF TUB SHALL BE A MAX.OF 6" |
| | ABOVE TUB.SEE FED.FAIR HOUSING ACT 24 |
| | CFR 100.205. |
| | |
| | RELIEF LINES FROM EWH SHALL NOT BE |
| | TRAPPED PER COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.507.8.4. |
| | |
| | HEATER PANS SHALL COMPLY W/SPC SEC. |
| | 507.8.2. |
| | |
| | SUBMIT ENERGY CALCS.AND EF RATING OF EWH |
| | PER FLA.ENERGY CODE SEC.103.2. |
| | |
| | SHOW FIXTURE UNIT LOAD ON SANITARY RISER |
| | (STACKS AND HORIZONTAL DRAINS.)COMPLY W/ |
| | SPC TABLES 714.1,714.2. |
| | |
| | SIZE ALL PORTIONS OF THE DWVSYSTEM. |
| | (CHECK ALL RISERS-SIZES MISSING FROM |
| | BUILDING DRAINS,BRANCHES,AND VENTS) |
| | |
| | THE CLEAR FLOOR SPACE PROVIDED AT SINKS |
| | SHALL BE CENTERED ON THE BOWL PER FED. |
| | FAIR HOUSING ACT 24 CFR 100.205 (C)(3) |
| | (IV) REQ.#7(1). |