| Plan Review Notes For Permit 00020799 |
| Permit Number |
00020799 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE:NEED TO LABEL ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED. AS REQ`D BY 210-8-A-6 | | | | | | 2)NOTE:PLEASE CORRECT WIRE SIZE GOING TO | | | ALL PANELS. YOU SHOW #3 BEING PROTECTED | | | BY A 125 AMP BRKR. TABLE 310-16 75C | | | COLUMN,,,WIRE IS ONLY RATED FOR 100AMPS. | | | | | | 3)NOTE; YOU ARE SHOWING A/C LOAD AT 100% | | | THIS SEEMS TO BE THE DERATED LOAD??? | | | PLEASE SHOW SIZE OF THE ORIGINAL HEAT | | | STRIP.SEE AP-E8.01 | | | | | | 4)NOTE: PLEASE SHOW THE LOAD ON "HP" | | | AS BEING CONTINUOUS. | | | | | | PLEASE SUBMIT THE ABOVE INFORAMTION | | | FOR REVIEW AND APPROVAL.IF THERE ARE ANY | | | QEUSTIONS PLEASE CALL 659-8096 EXT 8372 |
|