| Plan Review Notes For Permit 00020690 |
| Permit Number |
00020690 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************ UNSAT ******************** | | | | | | 1)NOTE: NEED TO PROVIDE DISCONNECT IN - | | | LINE FROM GENERATOR TO TRANSFER SWITCH. | | | AS PER 225-31 | | | ALSO MAINS MUST BE GROUPED PER 230-70/ | | | 230-72 AND ALL MUST BE MARKED PER NEC. | | | 1 OF? 2 OF? ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|