2001-01-08 00:00:00************ UNSAT ********************
  
 1)NOTE: NEED TO PROVIDE DISCONNECT IN -
 LINE FROM GENERATOR TO TRANSFER SWITCH.
 AS PER 225-31
 ALSO MAINS MUST BE GROUPED PER 230-70/
 230-72 AND ALL MUST BE MARKED PER NEC.
 1 OF? 2 OF? ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372