| Plan Review Notes For Permit 00020683 |
| Permit Number |
00020683 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** PROVISO **************** | | | | | | 1)NOTE: LOAD CALCULATION DOES NOT MEET | | | ART 220 OF THE NEC . PLEASE CORRECT. | | | | | | 2)NOTE: EQUIPMENT GROUNDING CONDUCTOR | | | IS REQ`D FROM MAIN HOUSE IN CONDUIT WITH | | | FEEDERS FOR PANEL. SIZE PER 250-122 | | | | | | 3)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BLDG. STEEL AS PER 250-50 AND | | | ANY METAL COLD WATER PIPE AT DETACHED | | | BLDG. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ANY ROUGH ELECTRICAL IS | | | CALLED IN. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|