| Plan Review Notes For Permit 00020679 |
| Permit Number |
00020679 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SHOW ALL SMOKE DETECTORS | | | REQ`D INSIDE AND OUTSIDE ALL SLEEPING | | | ROOMS OF NEW DWELLINGS.THESE ARE REQ`D | | | BY 1993/1996 NFPA-72 2-2.1.1.1. | | | | | | 2)NOTE: PLANS SHOW MAIN DISCONNECT? | | | RISER DIAGRAM DOES NOT? PLEASE CORRECT | | | PLANS. | | | | | | 3)NOTE: 410-8 EVEN FLOURESCENT LIGHTING | | | MAY NOT BE ABOVE STORAGE SHELF IN MASTER | | | BEDROOM CLOSET. | | | | | | 4)NOTE: PLEASE NOTE THE MISSING OUTLETS | | | REQ`D BY 210-52 IN TWO BEDROOMS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|