Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL SMOKE DETECTORS
 REQ`D INSIDE AND OUTSIDE ALL SLEEPING
 ROOMS OF NEW DWELLINGS.THESE ARE REQ`D
 BY 1993/1996 NFPA-72 2-2.1.1.1.
  
 2)NOTE: PLANS SHOW MAIN DISCONNECT?
 RISER DIAGRAM DOES NOT? PLEASE CORRECT
 PLANS.
  
 3)NOTE: 410-8 EVEN FLOURESCENT LIGHTING
 MAY NOT BE ABOVE STORAGE SHELF IN MASTER
 BEDROOM CLOSET.
  
 4)NOTE: PLEASE NOTE THE MISSING OUTLETS
 REQ`D BY 210-52 IN TWO BEDROOMS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372