| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | LOCATION OF PLUMBING FIXTURES ON | | | SANITARY RISER DOESN'T CORRELATE W/FLOOR | | | PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | WATER CLOSET IN 2ND.FLOOR MASTER BATH | | | NOT VENTED.SPC SEC.901.2. | | | | | | MAX.OF 4 FIXTURE UNITS PERMITTED ON 2" | | | WET VENT PER SPC.SEC.911.1.(1).(SEE 1ST. | | | FLR.M.B.) | | | | | | ONLY FIXTURE DRAINS PERMITTED ON WET | | | VENTS PER COUNTYWIDE AMENDMENTS TO SPC | | | SEC.911.1.1.(SEE 1ST.FLR.M.B.) |
|