| Plan Review Notes For Permit 00020599 |
| Permit Number |
00020599 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO SHOW A/C EQUIPMENT AND | | | DISCONNECT REQ`D BY 440-11 AND 215-5 | | | ALSO RECEPT. PER MECH CODE. | | | | | | 2)NOTE: PLEASE LIST THE REQ`D DEDICATED | | | BATH(S) CIRCUT PER 210-11-C-3.MUST BE | | | 20AMP AND #12 AWG. | | | | | | 3)NOTE: PLEASE SHOW THE EQUIPMENT GROUND | | | -ING CONDUCTOR REQ`D AND SIZE PER NEC | | | 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|