Plan Review Notes
Plan Review Notes For Permit 00020597
Permit Number 00020597
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: NEED TO SHOW EQUIPMENT GROUNDING
 CONDUCTOR REQ`D FROM MAIN TO PANEL.
 PLEASE SIZE PER 250-122
  
 2)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUT REQ`D BY 210-11-C-3 MUST
 BE #12 AND 20AMP.
  
 3)NOTE: PLEASE SHOW A/C EQUIPMENT AND
 THE REQ`D DISCONNECT BY 440-11 AND RECEP
  
 NEED TO SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372