Plan Review Notes
Plan Review Notes For Permit 00020596
Permit Number 00020596
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00LOCATION OF PLUMBING FIXTURES ON
 SANITARY RISER DOESN'T CORRELATE W/FLOOR
 PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 WATER CLOSET IN 2ND.FLR.BATH NOT VENTED.
 SPC SEC.901.2.
  
 MAX.OF 4 FIXTURE UNITS PERMITED ON 2"WET
 VENT PER SPC SEC.911.1(1). (SEE 1ST.FLR.
 MASTER BATH)
  
 ONLY FIXTURE DRAINS PERMITTED ON WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.(SEE 1ST.FLR.M.B.)