| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE SHOW A/C EQUIPMENT AND | | | DISCONNECT REQ`D BY 440-11. ALSO RECEPT. | | | | | | | | | 2)NOTE: PLEASE LIST ON PANEL SCHEDULE | | | THE REQ`D DEDICATED BATH(S) CIRCUT(S) | | | BY 210-11-C-3 MUST BE 20 AMP AND #12 | | | | | | 3)NOTE: NEED TO SHOW THE REQ`D EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | | PANEL. SIZE PER 250-122 | | | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL.IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|