Plan Review Notes
Plan Review Notes For Permit 00020596
Permit Number 00020596
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE SHOW A/C EQUIPMENT AND
 DISCONNECT REQ`D BY 440-11. ALSO RECEPT.
  
  
 2)NOTE: PLEASE LIST ON PANEL SCHEDULE
 THE REQ`D DEDICATED BATH(S) CIRCUT(S)
 BY 210-11-C-3 MUST BE 20 AMP AND #12
  
 3)NOTE: NEED TO SHOW THE REQ`D EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. SIZE PER 250-122
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372