| Plan Review Notes For Permit 00020512 |
| Permit Number |
00020512 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF THE | | | MAIN DISCONNECTS. MAINS MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT. PER | | | 110-9/110-10 | | | | | | 2)NOTE: PLEASE DRAW MAIN DISCONNECTS | | | NEXT TO METER ON PLANS 215-5 | | | | | | 3)NOTE:PLEASE INDICATE ON RISER DIAGRAM | | | EQUIPMENT GROUNDING CONDUCTOR REQ`D | | | AFTER THE FIRST MEANS OF DISC. SIZE PER | | | 250-122 | | | | | | 4)NOTE:IF COLD WATER PIPE IN HOUSE IS | | | GOING TO BE METAL THEN IT MUST BE | | | INCLUDED AS PART OF THE GROUNDING ELEC- | | | -TRODE SYSTEM. PER 250-50 | | | | | | 5)NOTE: PLEASE LIST ON PANEL SCHEDULE | | | THE REQ`D BATH(S) CIRCUT(S). MUST BE | | | 20AMP AND #12 AWG REQ`D BY 210-11-C-3 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 | | | EXT 8372 |
|