2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF THE
 MAIN DISCONNECTS. MAINS MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT. PER
 110-9/110-10
  
 2)NOTE: PLEASE DRAW MAIN DISCONNECTS
 NEXT TO METER ON PLANS 215-5
  
 3)NOTE:PLEASE INDICATE ON RISER DIAGRAM
 EQUIPMENT GROUNDING CONDUCTOR REQ`D
 AFTER THE FIRST MEANS OF DISC. SIZE PER
 250-122
  
 4)NOTE:IF COLD WATER PIPE IN HOUSE IS
 GOING TO BE METAL THEN IT MUST BE
 INCLUDED AS PART OF THE GROUNDING ELEC-
 -TRODE SYSTEM. PER 250-50
  
 5)NOTE: PLEASE LIST ON PANEL SCHEDULE
 THE REQ`D BATH(S) CIRCUT(S). MUST BE
 20AMP AND #12 AWG REQ`D BY 210-11-C-3
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372