Plan Review Notes
Plan Review Notes For Permit 00020484
Permit Number 00020484
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** PROVISO*****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF NEW
 PANEL. MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT. 110-9/110-10
  
 2)NOTE: PLEASE INDICATE THAT ALL CIRCUTS
 FROM BAY #3 ARE TO BE FED FROM PANEL IN
 BAY #3. ALL CIRCUTS IN BAY #4 ARE TO BE
 FED FROM PANEL IN BAY #4. INDCATE THIS
 ON PLANS.
  
 3)NOTE: PLEASE SHOW ALL CIRCUT #`S ON
 PLANS FOR NEW PANEL.
  
 4)NOTE: NEED TO SHOW HEIGHTS OF DEVICES
 IN BATH TO MEET ADA.
  
 PLEASE SUBMIT FOR REVIEW AND APPROVAL.
 BEFORE FIRST ROUGH ELECTRICAL INSPECTION
 659-8096 EXT 8372