| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** PROVISO***************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF NEW | | | PANEL. MUST BE RATED FOR THE AVAILABLE | | | FAULT CURRENT. 110-9/110-10 | | | | | | 2)NOTE: PLEASE INDICATE THAT ALL CIRCUTS | | | FROM BAY #3 ARE TO BE FED FROM PANEL IN | | | BAY #3. ALL CIRCUTS IN BAY #4 ARE TO BE | | | FED FROM PANEL IN BAY #4. INDCATE THIS | | | ON PLANS. | | | | | | 3)NOTE: PLEASE SHOW ALL CIRCUT #`S ON | | | PLANS FOR NEW PANEL. | | | | | | 4)NOTE: NEED TO SHOW HEIGHTS OF DEVICES | | | IN BATH TO MEET ADA. | | | | | | PLEASE SUBMIT FOR REVIEW AND APPROVAL. | | | BEFORE FIRST ROUGH ELECTRICAL INSPECTION | | | 659-8096 EXT 8372 |
|