Plan Review Notes
Plan Review Notes For Permit 00020469
Permit Number 00020469
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************ UNSAT ********************
  
 1)NOTE: NEED TO SHOW GROUNDING ELECTRODE
 SYSTEM. TO BLDG.STEEL OF NEW ADDITION.
 NEEDS TO GO TO COLD WATER PIPE AND
 GROUND ROD. PER 250-81
  
 2)NOTE: 1 3/4 CONDUIT IS NOT A STANDARD
 SIZE. PLEASE CORRECT.
  
 3)NOTE:NEED TO SUBMIT THE AIC RATING OF
 EQUIPMENT MAINS. MAIN MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT. AS REQ`D BY
 ART:110-9/110-10. 215-5
  
 4)NOTE: PLEASE CHECK LOAD CALCULATIONS,,
 YOU SHOW ONLY ONE SMALL APPLIANCE CIRCUT
 ???? TWO REQ`D BY CODE.
 WHAT IS BEING USED FOR A/C, HEAT???
 IF THERE IS CENTRAL AIR THEN IT IS TO BE
 CALCUALTED.
 ALSO 40% OF 6553 IS NOT 262. PLEASE
 CORRECT THIS FIGURE FOR LOAD.
 IF THERE ARE INDIVIDUAL WALL A/C UNITS,
 THEN FIGURE NAMEPLATE RATINGS.
  
 NEED TO HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 659-8096 EXT 8372