| Plan Review Notes For Permit 00020421 |
| Permit Number |
00020421 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE:PLEASE SUBMIT AIC RATING OF NEW | | | EQUIPMENT. AIC RATING MUST BE RATED FOR | | | THE AVAILABLE FALUT CURRENT.110-9/110-10 | | | | | | 2)NOTE: SMOKE DETECTORS REQ`ED INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS.AS PER | | | NFPA-72 2-2.1.1.1 | | | | | | 3) NOTE: PANEL IN KITCHEN PANTRY/CLOSET | | | NOT PERMITTED. THIS APPEARS TO BE A | | | KITCHEN CLOSET AREA FOR STORAGE. IF THIS | | | IS THE LOCATION WHERE THE PANEL IS GOING | | | TO BE INSTALLED, THEN THE PLANS ARE TO | | | HAVE THAT ROOM LABELED AS A ELECTRICAL | | | EQUIPMENT ROOM. IT SHALL BE ONLY FOR | | | ELEC. EQUIPMENT. ART:384. AND 110-16 | | | | | | 4)NOTE: PLEASE INDICATE ON PANEL SCHED. | | | THE DEDICATED BATH(S) CIRCUT REQ`D BY | | | ART: 210-52D. WHICH REQ`S #12 20AMP | | | CIRCUT. | | | | | | JUST A NOTE THAT A/C EQUIPMENT MUST MAIN | | | TAIN DISTANCE FROM POOL EDGE. | | | | | | PLEASE SUBMIT THE PLANS WITH THE ABOVE | | | INFORMATION FOR REVIEW AND APPROVAL. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|