Plan Review Notes
Plan Review Notes For Permit 00020421
Permit Number 00020421
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ***************
  
 1)NOTE:PLEASE SUBMIT AIC RATING OF NEW
 EQUIPMENT. AIC RATING MUST BE RATED FOR
 THE AVAILABLE FALUT CURRENT.110-9/110-10
  
 2)NOTE: SMOKE DETECTORS REQ`ED INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS.AS PER
 NFPA-72 2-2.1.1.1
  
 3) NOTE: PANEL IN KITCHEN PANTRY/CLOSET
 NOT PERMITTED. THIS APPEARS TO BE A
 KITCHEN CLOSET AREA FOR STORAGE. IF THIS
 IS THE LOCATION WHERE THE PANEL IS GOING
 TO BE INSTALLED, THEN THE PLANS ARE TO
 HAVE THAT ROOM LABELED AS A ELECTRICAL
 EQUIPMENT ROOM. IT SHALL BE ONLY FOR
 ELEC. EQUIPMENT. ART:384. AND 110-16
  
 4)NOTE: PLEASE INDICATE ON PANEL SCHED.
 THE DEDICATED BATH(S) CIRCUT REQ`D BY
 ART: 210-52D. WHICH REQ`S #12 20AMP
 CIRCUT.
  
 JUST A NOTE THAT A/C EQUIPMENT MUST MAIN
 TAIN DISTANCE FROM POOL EDGE.
  
 PLEASE SUBMIT THE PLANS WITH THE ABOVE
 INFORMATION FOR REVIEW AND APPROVAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372