| Plan Review Notes For Permit 00020363 |
| Permit Number |
00020363 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED; | | | ALL PROBLEMS IN QUEST QUARTERS; | | | 1.FIRST FLOOR CFM'S REQUIRED FOR ALL | | | DROPS. | | | 2.SECOND FLOOR, RETURN AIR NOT PERMITED | | | IN BATHROOM. | | | 3.A/C UNIT TO SMALL FOR CFM'S SHOWN. | | | 790 CFM WITH ONE DROP MISSING | | | CALCULATIONS. 1 1/2 TON A/H WILL | | | PROVIDE ONLY 600 CFM. |
|