| 2001-01-08 00:00:00 | 1)PLANS SHALL BE REVIEWED AND APPROVED |
| | BY THE DEPT.OF BUSINESS REGULATION |
| | PER COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 101.4.7. |
| | |
| | 2)SHT.P7.1-PREMIER BAR AREA-PLAN VIEW |
| | SHOWS A FLOOR SINK AND THE SANITARY |
| | RISER SHOWS A HAND SINK.CLARIFY. |
| | |
| | 3)SHT.P8-SEE REVISION DELTA 14-SHOW |
| | LOCATION OF THIS PIPING ON THE PLAN |
| | VIEW.COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 104.2.1. |
| | |
| | 4)SHT.P8-PREMIER BAR AREA-SIZE ALL |
| | SECTIONS OF THE DWV SYSTEM.COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | 5)CONTACT R.COMPO W/CITY OF WPB |
| | UTILITIES FOR APPROVAL OF WASTE FROM |
| | ELEVATORS TO SANITARY SYSTEM.CALL |
| | 561-835-7423. |
| | |
| | 6)SHT.P8-SHOW LOCATION OF TERMINATION |
| | POINT OF 3"DRAIN FROM OIL INTERCEPTOR. |
| | |
| | 7)TWO WAY CLEANOUTS ARE REQD.ENTERING |
| | AND LEAVING INTERCEPTORS.SPC SEC.710.4. |
| | |
| | 8)WATER HEATERS SHALL BE READILY |
| | ACCESSIBLE.SPC 507.1. |
| | |
| | 9)SHT.P9.1-WATER SUPPLY CONTROL SHALL |
| | COMPLY W/SPC SEC.610.4.2.(VALVES ARE |
| | REQD.ON THE BRANCH LINES.) |
| | |
| | 10)CLEARLY SHOW THE LOCATIONS OF THE |
| | INTERCEPTORS ON THE PLANS.SPC 104.2.1. |
| | |
| | 11)CLEARLY LABEL RISERS,STACKS ,ETC.FOR |
| | IDENTIFICATION AND LOCATION.COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |