Plan Review Notes
Plan Review Notes For Permit 00020337
Permit Number 00020337
Review Stop P
Sequence Number 7
Notes
Date Text
2001-01-08 00:00:00SUBMIT MANUF.SHEETS/DETAIL OF OIL
 INTERCEPTOR.SPC SEC.1004.2.
  
 CLEARLY IDENTIFY SPACE/LOCATION OF OIL
 INTERCEPTOR.INTERCEPTOR SHALL BE
 ACCESSIBLE.SPC SEC.1004.8.
  
 SUBMIT SANITARY AND WATER ISOMETRICS FOR
 THE CHANGES TO THE SYSTEMS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 SHT.P-7-INDICATE THE FLOOR LEVEL OF
 THE STRUCTURE FOR THESE CHANGES.SPC SEC.
 104.2.1.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.PROVIDE FIXED LADDER
 OR RELOCATE WATER HEATER TO FLOOR.