Plan Review Notes
Plan Review Notes For Permit 00020337
Permit Number 00020337
Review Stop M
Sequence Number 7
Notes
Date Text
2001-01-08 00:00:00DENIED FOR MECHANICAL RESPECTIVE OF THE
 PLAN TO START UP BY STAGES OF THE AIR
 CONDITIONING AND PERMANENT POWER FOR
 MUVICO
  
 AFTER REVIEWING THE COMMENTS BY THE FIRE
 PLAN REVIEW AND ELECTRICAL PLAN REVIEW
 THE MECHANICAL ASPECTS OF THIS PROPOSED
 STARTUP ARE DENIED.
 THE PERMANENT POWER AND AIR CONDITIONING
 SHOULD NOT BE ALLOWED UNTIL FIRE ALARM
 AND FIRE SPRINKLER SYSTEMS ARE IN PLACE
 ANDFUNCTIONAL. THIS WAS ADDRESSED AT
 TIME OF THE ORIGINAL MEETING DISCUSSING
 THIS DEPARTMENTS REQUIREMENTS PRIOR TO
 PERMANENT POWER BEING RELEASED
 GENERALLY THERE IS NO PROBLEM WITH THE
 PROPOSED PHASING OF MECHANICAL SYSTEMS
 ONCE THE ISSUES FROM FIRE AND ELECTRICAL
 ARE ADDRESSED