Plan Review Notes
Plan Review Notes For Permit 00020337
Permit Number 00020337
Review Stop M
Sequence Number 6
Notes
Date Text
2001-01-08 00:00:00********DENIED*************************
  
 1) REVISION 8 INDICATES UTILIZING GYP.
 BD. ENCLOSURE AS AIR PLENUM ELIMINATING
 DUCT AND SMOKE FIRE DAMPERS AS INDICATED
 ON MECH REVISION 6.
 2)1997 SBC 705.2.2 REQUIRES SHAFT ENCLOS
 URES AT ALL PENETRATIONS OF FLOOR OPEN-
 INGS. PROVIDE SHAFT DETAIL INCLUDING
 RATING FOR ABOVE ENCLOSURES
 3) BLDG REVISION 8 SAYS SEE MECH DRAWING
 NO MECHANICAL DRAWINGS INCLUDED WITH
 THIS REVISION. MECHANICAL REVISION REQ'D
 TO PROVIDE COMPLETE REVIEW OF THIS
 CHANGE