Plan Review Notes
Plan Review Notes For Permit 00020337
Permit Number 00020337
Review Stop P
Sequence Number 5
Notes
Date Text
2001-01-08 00:00:00*******************PROVISO**************
  
 THE LAYOUT OF THE GREASY WASTE SYSTEM ON
 THE PLAN VIEW ON SHT.P-1 DOESN'T CORR-
 ELATE W/THE SANITARY RISER ON SHT.P-8.
  
 THE SIZE OF THE GREASE TRAP SHALL BE
 APPROVED BY THE CITY OF WEST PALM BEACH
 UTILITIES.CONTACT ROD COMPO AT
 (561)835-7423.SUBMIT APPROVAL FORM FROM
 UTILITIES.
  
 DISCHARGE FROM ELEVATOR SUMPS SHALL
 CONNECT TO THE SANITARY SYSTEM.
  
 WATER RISER-OVER 4 FIXTURE CONNECTED TO
 1/2"H.W.LINE.COUNTYWIDE AMENDMENTS TO
 SPC SEC.607.7.
  
 LINE SIZES ARE LACKING ON THE WATER
 RISER AND STORM RISER.
  
 SHT.8.1-10"STORM DRAIN DRAINING INTO 8"
 LINE.SEE RISER ST-5.SPC 709.1.