Plan Review Notes For Permit 00020337
Permit Number 00020337
Review Stop M
Sequence Number 5
Notes
Date Text
2001-01-08 00:00:00FAILED
  
 1) SLOPE FOR GREASE DUCT MIN. 1" PER 12"
 PER 1997 SMC 505.4
 2) PROVIDE SPECIFIC DETAIL FOR KITCHEN
 DUCT AND HOODS AT TIME OF PERMIT APPLICA
 TION FOR HOOD INSTALLATION PRIOR TO ANY
 WORK ON HOOD OR DUCT SYSTEM
 3) EXHAUST DUCT TO BE RUN IN ENCLOSURE
 DEDICATED TO SINGLE EXHAUST DUCT AND FOR
 NO OTHER PURPOSE
 4) MIN CLEARANCE FROM DUCT TO INSIDE OF
 ENCLOSURE IS 6"